Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On
-Line System IMx-M
2 - 101
User Manual
Figure 2 - 85.
Initiating an Analog Channel.
Type:
Currently permitted analog channel types are the following.
Temperature
applies to channels 9 to 16 only.
For detailed information refer to the measurement type Temperature.
Radial shaft vibration
type is available on all channels.
For detained information refer to the measurement type Radial Shaft Vibration
and the configuration example of a Radial shaft vibration channel.
Position
type is available on all channels.
For detailed information refer to the measurement type Position.
Complementary Differential Expansion
uses signals from two channels of
combined measurements to extend measurement range. This type has to be
one of a combined measurements.
For detailed information refer to the measurement type Complementary
Differential Expansion and the configuration example of Complementary
Differential Expansion.
Piston Rod Drop (Average Mode)
measures the displacement of the piston
rod over the entire cycle. This type is available on all channels.
For detailed information refer to the measurement type Piston Rod Drop and
the configuration example of Piston Rod Drop.
Piston Rod Drop (Triggered Mode)
type is available on all channels.
For detailed information refer to the measurement type Piston Rod Drop and
the configuration example of Piston Rod Drop.
Casing vibration
type is available on all channels.
For detailed information refer to the measurement type Casing Vibration and
the configuration example of a Casing vibration channel.
Eccentricity
type is available on all channels.
For detailed information refer to the measurement type Eccentricity.