Protection
Modbus
2 - 182
SKF Multilog O
n-Line System IMx-M
User Manual
Register "Analog Ch Status" Bit Definition
Bit representation* Description
0x0008
Ch danger
0x0010
Ch danger first out slot
0x0020
Ch circuit fault. Note: Ch circuit fault overrides all other status.
For CDE combined measurement: if both corresponding channels X and Y are in ch
circuit faults, the CDE combined measurement will be in ch circuit fault.
For other types of combined measurements: if a corresponding channel X or channel Y is
in ch circuit fault, the combined measurement will be in ch circuit fault.
0x0040
Ch disarmed
For all types of combined measurements: if a corresponding channel X or channel Y is in
channel disarm, then the combined measurement will be set to channel disarm.
0x0080
Slot disarmed
For all types of combined measurements: if corresponding channels X and Y are in slot
disarm, then the combined measurement will be set to slot disarm.
0x0100
Trip multiply
0x0200
Ch is a part of CDE setup but not used for the moment
0x0400
Ch danger first out of rack
0x0800
Ch Gap alert
0x1000
Ch Gap danger
*
Important:
- Bit representation is in hexadecimal digits.
- Bit representation can be a combination of more than one condition.
Example:
Bit representation of 0x016A is equal to 0x0002 Ch alert +
0x0008 Ch
0x0020 Ch circuit fault +
0x0040 Ch di
0x0100 Trip multiply
Refer to Bit Representation of Combined Conditions for combined conditions.