User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Most important parameters of S8, S16 and S24 modules:
S8
S16
S24
Static parameters
Number of outputs
8
16 (in 2 groups with
separate supply)
24 (in 3 groups with
separate supply)
Max current source per
output:
while
powered internally
while
powered externally
10mA,
sum limited to 50mA
100mA,
sum limited to 500mA
10mA,
sum limited to 50mA
for a group
100mA,
sum limited to 500mA
for a group
10mA,
sum limited to 50mA
for a group
100mA,
sum limited to 500mA
for a group
Output High Level voltage
(Iout = 5mA)
while
powered internally
while
powered externally
≥ 8V
≥ (Vext. - 0.5V)
≥ 8V
≥ (Vext. - 0.5V)
≥ 8V
≥ (Vext. - 0.5V)
Output Low Level voltage
(Iout = 5mA)
<1V
<1V
<1V
Overload protection
while
powered internally
while
powered externally
Internal fuse 50mA
Internal fuse 500mA
Internal fuse 50mA
(per group)
Internal fuse 500mA
(per group)
Internal fuse 50mA
(per group)
Internal fuse 500mA
(per group)
Maximum external supply
of output *
30 V
30 V
30 V
Dynamic parameters (set individually for every output)
PWM period **
0.1 ÷ 1600 sec.
0.1 ÷ 1600 sec.
0.1 ÷ 1600 sec.
PWM resolution
0.1 sec.
0.1 sec.
0.1 sec.
PWM internal frequency** 5kHz***
5kHz***
5kHz***
Pulse - duty factor
0 ÷ 100%
0 ÷ 100%
0 ÷ 100%
Pulse - duty factor
resolution
15 bits **
0x8000 means 100%
15 bits**
0x8000 means 100%
15 bits**
0x8000 means 100%
Lo state minimum time
limit
0 ÷ 800 sec.
0 ÷ 800 sec.
0 ÷ 800 sec.
Hi state minimum time
limit
0 ÷ 800 sec.
0 ÷ 800 sec.
0 ÷ 800 sec.
Isolation strength
1 min. @ 500V AC
1 min. @ 500V AC
1 min. @ 500V AC
Weight
48 g
68 g
74 g
* Minimum external supply voltage is 10V, if external supply is less than 10V then outputs are powered
internally
269