User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
type
range* resolution
full range
full range accuracy
limited range
limited range accuracy
[ mV ]
[ μV ]
[
°C
]
[
°C
]
[ % ]
[
°C
]
[
°C
]
[ % ]
K
±120
4
-200÷1370
±8
±0.51
-100÷1370
±4
±0.27
S
±30
1
-50÷1768
±7.5
±0.41
0÷1768
±6
±0.34
J
±120
4
-210÷1200
±6.3
±0.44
-100÷1200
±3
±0.23
T
±30
1
-200÷400
±1.9
±0.31
-100÷400
±1
±0.20
N
±120
4
-200÷1300
±12
±0.80
-100÷1300
±5.9
±0.42
R
±30
1
-50÷1768
±8.6
±0.47
0÷1768
±5.5
±0.31
E
±120
4
-200÷1000
±4.7
±0.40
-100÷1000
±2.7
±0.25
L
±120
4
-200÷800
±4.4
±0.44
-100÷800
±2.5
±0.28
B
±30
1
250÷1820
±15
±0,96
480÷1820
±6
±0,45
C
±120
4
50÷2290
±13
±0,51
50÷1900
±9,2
±0,5
* with consideration of device working in -20'C÷50'C of ambient temperature.
Tab. 8.8 Measurement accuracy for the module TC4, TC8, TC12
type
norm
K
PN-EN 60584-1:2014
S
PN-EN 60584-1:2014
J
PN-EN 60584-1:2014
T
PN-EN 60584-1:2014
N
PN-EN 60584-1:2014
R
PN-EN 60584-1:2014
E
PN-EN 60584-1:2014
L
GOST R 8.595:2004
B
PN-EN 60584-1:2014
C
PN-EN 60584-1:2014
Tab. 8.9 Thermocouple norm for the module TC4, TC8, TC12
251