User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
–
Maximal value
– available for certain math functions, constant value which will be
maximal value for the function,
–
Averaging time
– available for
Function=avarege of X
, determines logical channel
amount of samples which fits in this time and will be averaged; after this time
function enters a saturated state,
–
Reset now
– button available for certain math functions, asynchronously resets
function value,
–
Reset mode
– available for some math functions, depending on this parameter, the
user can set following options:
•
disabled
– means that function after reaching maximal value, will stop on this
value,
•
automatic
– means that function after reaching maximal value will axiomatically
resets it self and returns to initial value,
•
from log. channel
– means that function reset is triggered from selected logical
channel,
–
Reset source
– available for some math functions, selects a logical channel which
will be reset source for the function,
–
Reset triggering
– available for some math functions, allows to select triggering
method from the logical channel, the user can set following options:
•
high level
– function resets when resetting channel is in high state,
•
low level
– function resets when resetting channel is in low state,
•
rising edge
– function resets when in resetting channel rising edge occurs,
•
falling edge
– function resets when in resetting channel falling edge occurs,
–
J input mode
– available for
Function=flip flop
, the user can set following options:
•
always 0
– flip flop J input is always in logical state '0',
•
always 1
– flip flop J input is always in logical state '1',
•
from log. channel
– means that flip-flop J input source will be logical state
value of selected logical channel,
•
from channel (negation)
– means that flip-flop J input source will be negated
logical state value of selected logical channel,
–
J input source
– available for
Function=flip flop
, selects a logical channel which
will be source for flip-flop J input,
–
K input mode
– available for
Function=flip flop
, the user can set following options:
•
always 0
– flip flop K input is always in logical state '0',
•
always 1
– flip flop K input is always in logical state '1',
•
from log. channel
– means that flip-flop K input source will be logical state
value of selected logical channel,
•
from channel (negation)
– means that flip-flop K input source will be negated
logical state value of selected logical channel,
–
K input source
– available for
Function=flip flop
, selects a logical channel which
will be source for flip-flop K input,
–
Clock source
– available for
Function=flip flop
but unavailable if parameters
J input mode
and
K input mode
are both set as always 0, allows to select a logical
channel which will be flip-flop clock input source,
–
Clock triggering
– available for
Function=flip flop
, the user can set following
options:
•
high level
– flip-flop triggers when in selected in
Clock source
parameter
channel is in high logical state,
•
low level
– flip-flop triggers when in selected in
Clock source
parameter
channel is in low logical state,
97