User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
◦
in the
Decimal point
parameter select option: * exp (-point register) causes
that will be appear a new parameter to appear -
Decimal point register
that causes an automatic change of decimal point, depending on value of
Decimal point register
,
◦
in the
Decimal point register
parameter set:
–
Register type: HOLDING
,
–
Register number: 3h
,
–
Data format: 16 bits, unsigned
,
–
Data shift: 0
,
–
Data mask: 0x0003
, because the interest to us only the first 2 bits
changing register value, the value of which determines the decimal
point, exit after the settings this menu,
•
-HI- state
parameter set as
if register = value
,
◦
in the
-HI- register
parameter set:
–
Register type
parameter set as
HOLDING
,
–
in
Register number
parameter write
2h
,
–
Data format
parameter set as
16 bits, unsigned
,
–
in
Data shift
parameter write
0
,
–
in
Data mask
parameter write
0x0080
,
◦
in the
-HI- value
parameter for the signal
-HI-
set the value of
0x0080
,
•
-LO- state
parameter set as
if register = value
,
◦
in the
-LO- register
parameter set:
–
Register type
parameter set as
HOLDING
,
–
in
Register number
parameter write
2h
,
–
Data format
parameter set as
16 bits, unsigned
,
–
in
Data shift
parameter write
0
,
–
in
Data mask
parameter write
0x0040
◦
in the
-HI- value
parameter for the signal
-HI-
set the value of
0x0040
,
•
-ERR- state
parameter set as
if register ≠ value
,
◦
in the
-ERR- register
parameter set:
–
Register type
parameter set as
HOLDING
,
–
in
Register number
parameter write
2h
,
–
Data format
parameter set as
16 bits, unsigned
,
–
in
Data shift
parameter write
0
,
–
in
Data mask
parameter write
0x00C0
,
◦
in the
-HI- value
parameter for the signal
-HI-
set the value of
0x0000
,
•
Blocks configuration mode
parameter set as
automatic
,
•
Max.block size
parameter set as
5
, because the slave device selected in this
example allows reading frame (using the Modbus function 03h) with up to 5
registers,
•
move to the
Device templates
parameter block and press
Save device template
button,
◦
in the
Save device template
menu, enter the template name, eg
Temperature converter
(stored template can be used to configure the
device to a different address),
219