User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
For reading temperature from PT100 sensor,
–
touch screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
logical channel
such as 2,
–
in
Name
parameter write
Feedback
,
–
Mode parameter set as Hardware input,
–
Source
parameters set as
Inp.A1 : RTD
–
enter
Configure source
submenu:
•
Mode
parameter set as
Pt100
,
•
in
Low Limit
parameter write
-100°C
,
•
in
High Limit
write
600°C
,
–
for
Displaying
block parameters:
•
Format
parameter set as
numeric
,
•
Precision
parameters set as
0.0
,
•
in
Graph low
write
0°C
,
•
in
Graph high
write
100°C
,
For channel settings in Controller mode:
–
touch screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
logical channel
such as 32,
–
in
Name
parameter write
Controller
,
–
Mode
parameter set as
Controller
,
–
in
Unit
parameters write
mA
,
–
Controller
number parameter set as
Controller 1
,
–
Set point channel
parameter set as logical channel 1 named
Setpoint
,
–
Feedback channel
parameters set as logical channel 2 named
Feedback
,
–
for
Displaying
block parameters:
•
Format
parameter set as
numeric
,
•
Precision
parameters set as
0.00
, because with this precision we can send
signal from controller to Current converter (see
•
in
Graph low
write
0
,
•
in
Graph high
write
10
,
For external output configuration (sending via RS-485) see
Chapter 7.11.4. Examples of
external output configurations
132