User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
–
for
Display
block parameters:
•
Format
parameter set as
numeric
,
•
Precision
parameter set as
0.0
, because Pt1000 sensor precision allows to
display its value with one decimal place,
•
in
Graph low
parameter write
15°C
,
•
in
Graph high
parameter write
30°C
,
Other channels set in the same way:
Logical channel 31:
Warehouse
,
Logical channel 32:
Basement
, in
Source configuration
set
Mode
parameter as PT100,
Logical channel 33:
Corridor
,in
Source configuration
set
Mode
parameter as PT100,
In the next step you need to define
Group
the set up logical channels to view them in one
window on the screen. To do this:
–
enter the
Group
menu, to enable the e.g.
Group 2
if it is off,
–
for
Display options
block parameters:
•
in
Name
parameter write
Workplace
,
•
Bars
parameter set as
vertical
,
–
for
Channels
block parameters:
•
Slot 1
parameter set as
Logical channel 30
called the
Office
,
•
Slot 2
parameter set as
Logical channel 31
called the
Warehouse
,
•
Slot 3
parameter set as
empty
,
•
Slot 4
parameter set as
Logical channel 32
called the
Basement
,
•
Slot 5
parameter set as
Logical channel 33
called the
Corridor
,
•
Slot 6
parameter set as
empty
,
–
for
Logging options
block parameters (this block of parameters appear if you have
license for logging):
•
Mode
parameter set as
always
, we want to register at all times until the we
change the configuration to stop the registration,
•
in
Description
parameter write M
easure of Workplace temperature
, (it can be
any text),
•
Base period
parameter set as
1
,
•
Base unit
parameter set as
minute
, sampling a group of channels at 1 minute,
•
Alternative mode parameter set as disabled,
The last step is to define the
Initial view
displayed on the LCD screen when the device starts.
Initial view has to display a defined group of logical channels: 30, 31, 32, 33 in bars mode. To
do this:
–
enter
General settings
menu,
–
for
Initial view
block parameters:
•
Display
mode
parameter set as
bars
,
•
Displayed group
parameter set as
Group 2: Workplace
,
Finally, you must exit the menu by pressing the
Save changes
button. The result of the
changes will be visible after a call to the first measurement and manual switch for displaying
Group 2. Example of a window view for 4 logical channels is shown in