User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
To read the output value from module:
–
touch screen and press the
Menu
button,
–
press
Device configuration
button,
–
enter the
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
Logical channel
such as 5,
–
in
Name
parameter write
Relay 1
,
–
Mode
parameter set as
Hardware output monitor
,
–
Source
parameter set as
Out. C1: Relay
–
for
Displaying
block parameters:
•
Format
parameter set as
binary
,
•
in
Off-state text
write
OFF
with red font color and yellow background,
•
in
On-state text
write
HI
with green font color and violet background,
•
in
Graph low
write
0
,
•
in
Graph high
write
1
,
In the next step you need to define
Group
the set up logical channels to view them in one
window on the screen. To do this:
–
enter the
Group
menu, to enable the
Group 1
if it is off,
–
in
Name
parameter write
Monitor output
,
–
for
Channels
block parameters,
•
Slot 1
parameter set as
Logical channel 5
called
Relay 1
,
•
other parameters in this block -
Slot 2÷6
, set as
disabled
, because we want to
show only one logical channel,
The last step is to define the
Initial view
displayed on the LCD screen when the device starts.
Initial View has to display a defined Group 1 in values mode. To do this:
–
enter
General settings
menu,
–
for
Initial view
block parameters:
•
Display
mode
parameter set as
value
,
•
Displayed group
parameter set as
Group 1: Output monitor
,
After whole configuration exit the menu pressing
Save changes
, the result will be visible
as soon as first measurement is done. View the window of MultiCon with the above
configuration is shown in
Fig. 7.68. The proposition of the result of the Example 4
124