User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
FI2
FI4
FT2
FT4
Input signals voltage
levels:
logical LOW state
logical HIGH state
-
-
-
-
| Uin | < 1V
| Uin | ≥ 10V
| Uin | < 1V
| Uin | ≥ 10V
Max input voltage
5V
5V
30V
30V
Sampling period
50ms
50ms
50ms
50ms
Max. input frequency
-
-
50kHz
50kHz
Totalizer capacity
1 000 000 000 000
1 000 000 000 000
1 000 000 000 000
1 000 000 000 000
Isolation strength
1 min. @ 500V AC
1 min. @ 500V AC
1 min. @ 500V AC
1 min. @ 500V AC
Weight
48 g
58 g
52 g
72 g
*
Measurement ranges are limited by software upon hardware inputs ability, check current list of
producer's website
Tab. 8.6 Technical data for the module FI2, FI4, FT2, FT4
Fig. 8.11. FT4 module and PNP type sensor connection scheme
247
PNP
Power supply
(depending on version)
1
2
8
5
6
7
3
4
SERVICE
+24V DC ±5%
(
I
max. = 200mA)
digital input
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
FT
4
4 pulse inputs
+ 4 current inputs
n15
n16
n17
n04
n05
n13
n14
n01
n02
n03
n04
n05
n01
n02
n03
n06
n10
n11
n07
n08
n09
n12
GND
IN5
IN6
IN7
IN8
4
x
0
-2
0m
A
COM4
Inp42
Inp41
COM3
Inp32
Inp31
COM2
Inp22
Inp21
COM1
Inp12
Inp11