User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
8.
APPENDICES
All connections must be made while power supply is disconnected !
8.1.
PS3, PS4, PS32, PS42 - POWER SUPPLY MODULE
Fig. 8.1 Power supply module: PS3 (left side), PS4, PS32 and PS42
–
If the
UN3
or
UN5
module is installed, the +24V DC output is available only in
devices equipped with
PS32
or
PS42
power supply module. In other cases there is
no
+24V
DC output
available and these terminals remain not used.
Most important parameters of PS3, PS4, PS32 and PS42 modules:
PS3
PS4
PS32
PS42
Number of
inputs/outputs
5
5
5
5
Power supply 19V...
24
...50V DC
16V...
24
...35V AC
85V...
230
...260 AC/DC
50 ÷ 60Hz
19V...
24
...50V DC
16V...
24
...35V AC
85V...
230
...260 AC/DC
50 ÷ 60Hz
USB
SERVICE
Service port
Sensor power
supply output
24V DC ±5% / max. 200mA
Digital input
0...15...24V DC with galvanic insulated
(low state:
0÷1V, high state:8÷24V)
power consumption: 7,5 mA / 24V,
insulation: 1min @ 500V DC.
Interface
RS-485, Modbus RTU, 1200bit/sec. ÷ 115200 bit/sec.
Weight
75 g
78,5 g
99 g
92 g
Tab. 8.1 Technical data for the power supply module PS3, PS4, PS32 and PS42
234
!
i
1
2
8
5
6
7
3
4
SERVICE
Wej. cyfrowe
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
+24V DC ±5%
I
max. = 200mA
Power supply
85V÷260V AC/DC
1
2
8
5
6
7
3
4
SERVICE
Wej. cyfrowe
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
+24V DC ±5%
I
max. = 200mA
Power supply
19V÷50V DC
16V÷35V AC
1
2
8
5
6
7
3
4
SERVICE
Wej. cyfrowe
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
+24V DC ±5%
I
max. = 200mA
PE
Power supply
19V÷50V DC
16V÷35V AC
1
2
8
5
6
7
3
4
SERVICE
Wej. cyfrowe
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
+24V DC ±5%
I
max. = 200mA
PE
Power supply
85V÷260V AC/DC