User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
7.14.3.
Groups - Examples of visualisations of groups
7.14.3.1.
Single channel - one big needle.
Task:
The task is to create Group with only one logical channel. The value of that channel
should be displayed in whole screen in needle mode.
Solution:
Let's assume that we have configured logical channel in Hardware input Mode for RTD
module. The logical channel is named Temperature and it displays heater temperature
(example of logical channels configuration are shown in
Chapter 7.8.11. Examples of
Logical Channels configuration
, especially see
7.8.11.3. Application of Logical channel
in the Hardware input mode for RT4 modules
We need to define Group with logical channel in order to display it on the device screen. To
do that:
–
enter
Groups
menu and turn on
Group 1
if it is turned off,
–
in
Name
parameter write
Heater
,
–
for
Channels
parameter block:
•
Slot 1
parameter set as
Logical channel 1
named
Temperature
,
•
Slot 2 ÷ 6
set as
disabled
,
–
all other parameter should be on default settings,
Next we need to define Initial view. To do this:
–
enter
General settings
menu,
–
for
Initial view
parameter block:
•
Display mode
parameter set as
needles
,
•
Displayed group
parameter set as
Group 1: Heater
,
Finally leave this menu and press Save settings button. Result of just made changes will be
visible after first measurement is called. Example of this view is posted in
Fig. 7.123. Single big needle example
200