User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Example 2:
Task:
User's task is to set blinking highlight on temperature channel, which will be activated on
three different levels.
Solution:
After connecting all measuring devices and configuring them in MultiCon, we can start to
configure the highlights.
To complete the task, we will need to configure 7 logical channels:
a) Channel with first level.
b) Channel with second level .
c) Channel with third level.
d) Channel that will tell when will first alarm appear.
e) Channel that will tell when will second alarm appear.
f) Channel that will tell when will third alarm appear.
g) Channel where the temperature is measured, and the alarms will appear.
Logical channel 1: First level:
–
In
Name
parameter write:
First level
,
–
Mode
parameter set as:
Set point value
,
–
Edit button
parameter set as:
enabled
,
–
In
Unit
parameter write:
°C
,
–
Precision
parameter set as:
0.0
,
–
In
Graph low
parameter write:
-50
,
–
In
Graph high
parameter write:
85
,
–
All other parameters should be set as default,
Logical channel 2: Second level:
–
In
Name
parameter write:
Second level
,
–
Mode
parameter set as:
Set point value
,
–
Edit button
parameter set as:
enabled
,
–
In
Unit
parameter write:
°C
,
–
Precision
parameter set as:
0.0
,
–
In
Graph low
parameter write:
-50
,
–
In
Graph high
parameter write:
85
,
–
All other parameters should be set as default,
Logical channel 3: Third level:
–
In
Name
parameter write:
Third level
,
–
Mode
parameter set as:
Set point value
,
–
Edit button
parameter set as:
enabled
,
–
In
Unit
parameter write:
°C
,
–
Precision
parameter set as:
0.0
,
–
In
Graph low
parameter write:
-50
,
–
In
Graph high
parameter write:
85
,
–
All other parameters should be set as default,
Logical channel 4: Calculating the time of the first alarm,
–
In
Name
parameter write:
Calc. First level
,
–
Mode
parameter set as:
Math function
,
–
Click on the
Function
button,
•
Function
parameter set as:
X – Y
,
81