6- 15
Installation Conditions and Method
6
(4) Input/output port
The input/output terminals are isolated by photocouplers, to prevent malfunctions due to noise.
Use them within the rated range. The specifications of the input/output ports are listed below.
12/24 VDC
10.5 to 26.4 VDC
ON: 10.5 V or less OFF: 5 V or more
ON: 3 mA or less OFF: 1.5 mA or more
3.3 k
ohm
12/24 VDC
10.5 to 27 VDC
20 mA DC
NPN transistor, open collector
1.2 V or less (20 mA)
Isolated by photocoupler
1 ms or less (OFF to ON, ON to OFF)
Rated input voltage
Input voltage range
Input voltage level
Input current level
Input impedance
Rated output voltage
Load voltage range
Rated max. output current
Output type
ON voltage drop
Isolation method
Input
Item Rating
Output
Response time
(5) Wiring to IV-S20 main housing
X0
X6
Y0
Y7
BUSY
-
+
+
-
C(+)
Power
supply
C(-)
Load
L
L
L
Input
Output
Fuse
(0.5A)
Power
supply
IV-S20
(3) Output terminals (OUTPUT) Y0 to Y7 and BUSY
Result of logical calculation output
- Specify in item
r
FINAL OUTPUT COND on the [OBJECT TYPE COND] menu.
=> See page 10-8 to 13.
Y0
to Y7
BUSY
When "BUSY" is active, this terminal outputs an ON signal while the IV-S20 is
executing the measurement and opening the all set menu.
When "READY" is active, this terminal outputs an ON signal while the IV-S20 is
waiting for a trigger.
- To specify "BUSY" or "READY," go to item
7
OUTPUT STATUS in the "I/O
SETTINGS" menu. Seetings => See page 11-1. Time chart, etc. => See page 11-
4 to 11-15.
(2) Input terminals (INPUT) X5 and X6
X6
Parallel selection input
(External input/image change etc. and measurement
number specification (upper bits))
Specify in item
6
PARALLEL INPUTX6 on the [I/O
SETTINGS] menu.
X5
Parallel selection input
(External input/reference image registration etc. and
measurement number specification (lower bits))
Specify in item
5
PARALLEL INPUTX5 on the [I/O
SETTINGS] menu.
(See page 11-1 and
11-2.)
Measurement 0
Measurement 0&1
Measurement 0&2
Measurement 0&3
OFF
OFF
ON
ON
OFF
ON
OFF
ON
Measurement
to be executed
X5
X6
[When X5 and X6 are used to
specify a measurement number]