95
Setting value Funtion
Pulse or analog output 0.0%~100.0% corresponding function
11
Count value
0 to maximum count value
12
Communication setting
0.0%
~
100.0%
13
Motor rotation speed
0
~
The rotation speed corresponding to maximum output
frequency
14
Output current
0.0A~1000.0A
15
BUS voltage
0.0V~1000.0V
06-09
DFM (P) output maximum frequency
Factory setting
50.00kHz
Setting range 0.01kHz
~
100.00kHz
When the DFM terminal is selected as the pulse output, this parameter is used to select the maximum frequency
value of the output pulse.
06-10
AFM zero offset coefficient
Factory setting
0.0%
Setting range -100.0%
~
+100.0%
06-11
AFM gain
Factory setting
1.00
Setting range -10.00
~
+10.00
06-12
AFM2 zero offset coefficient
Factory setting
0.0%
Setting range
-100.0%
~
+100.0%
06-13
AFM2 gain
Factory setting
1.00
Setting range
-10.00
~
+10.00
The above parameters are generally used to correct the zero drift of the analog output and the deviation of the
output amplitude. It can also be used to customize the desired AFM output curve.
If the zero offset is represented by "b", the gain is represented by k, the actual output is represented by Y, and the
standard output is represented by X, then the actual output is:
Y=kX+b. Among them, the zero deviation coefficient of AFM 100% corresponds to 10V, the standard output refers
to the amount of 0V ~ 10V corresponding to the analog output without zero deviation and gain correction.
06-17
MO1 output delay time
Factory setting
0.0s
06-18
Relay RA-RB-RC output delay time
Factory setting
0.0s
06-19
Reserved
Factory setting
06-20
Reserved
Factory setting
06-21
DFM(M) output delay time
Factory setting
0.0s
Setting range 0.0s
~
3600.0s
Set the delay time for the output terminal Terminal to change from the state to the actual output.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...