63
00-05
Lower limit frequency
Factory setting
0.00Hz
Setting range 0.00Hz
~
Upper limit frequency 00-04
When the frequency command is lower than the lower limit frequency set by 00-05, the inverter can be stopped,
run at the lower limit frequency or run at zero speed, and set the operation mode through 09-14 (the set frequency
is lower than the lower limit frequency operation mode).
00-06
Keyboard setting frequency
Factory setting
50.00Hz
Setting range 0.00
~
max frequency 00-03
When the frequency source is selected as "digital setting", the parameter value is the initial value of the frequency
digital setting of the inverter.
00-07
Acceleration time1
Factory setting
Type setting
Setting range 0.00s
~
65000s
00-08
Deceleration time 1
Factory setting
Type setting
Setting range 0.00s
~
65000s
The acceleration time refers to the time required for the inverter to accelerate from zero frequency to the
acceleration and deceleration base frequency (determined from 00-23), see t1 in Figure 5-1.
The deceleration time refers to the time required for the inverter to decelerate to the zero frequency from the base
frequency of acceleration and deceleration (determined from 00-23), see t2 in Figure 5-1
Output frequency
Hz
Acceleration/ deceleration
base frequency
Set acceleration time
Actual deceleration time
t1
Time
Set frequency
Actual acceleration time
Set deceleration time
t2
Figure 5-1 Schematic diagram of acceleration and deceleration time
S3100A provides 4 groups of acceleration and deceleration time, users can use the digital input terminal MI to
switch selection, the four groups of acceleration and deceleration time are set by the following parameters:
The first group: 00-07, 00-08; The second group: 09-03, 09-04; The third group: 09-05, 09-06; The fourth group:
09-07, 09-08.
00-09
Operation direction
Factory setting
0
Setting range
0
Forward
1
Reverse
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...