119
PI parameter
PI parameter 1
10-05
、
10-06
、
10-07
PID deviation
PI parameter 2
10-15
、
10-16
、
10-17
10-19
10-20
Figure 5-26 PID parameter switching
10-21
PID Initial value
Factory setting
0.0%
Setting range 0.0%
~
100.0%
10-22
PID initial value hold time
Factory setting
0.00s
Setting range 0.00s
~
650.00s
When the inverter starts, the PID output is fixed at the initial PID value of 10-21, and the PID will start the
closed-loop adjustment operation only after the initial PID holding time of 10-22.
Output frequency
PID initial value
10-21
Time
PID initial value hold time
10-22
Figure 5-27 Schematic diagram of PID initial value function
This function is used to limit the difference between two beats (2ms/beat) of PID output, so as to restrain the PID
output from changing too fast, and make the operation of the inverter tend to be stable.
10-23
Reserved
Factory setting
10-24
Reserved
Factory setting
10-25
PID feedback upper limit detection
Factory setting
0.0%
Setting range
0.0%: No judgment
0.1%
~
100.0%