Output overcurrent detection delay time
Factory setting
0.00s
Setting range
0.00s
~
600.00s
When the output current of the inverter is greater than or exceeds the limit detection point and the duration
exceeds the software overcurrent detection delay time, the inverter's multi-function output terminal (function 36)
outputs an ON signal. Figure 5-23 is a schematic diagram of the output overcurrent detection.
Output current
Time
Output current limit
09-36
Output overcurrent
detection signal
Time
ON
Output overcurrent
detection delay time 09-37
Figure 5-23 Schematic diagram of output overcurrent detection
09-38
Arbitrary arrival current 1
Factory setting
100.0%
Setting range 0.0%
~
300.0%(motor rated current)
09-39
Arbitrary arrival current 1 width
Factory setting
0.0%
Setting range 0.0%
~
300.0%(motor rated current)
09-40
Arbitrary arrival current 2
Factory setting
100.0%
Setting range 0.0%
~
300.0%(motor rated current)
09-41
Arbitrary arrival current 2 width
Factory setting
0.0%
Setting range 0.0%
~
300.0%(motor rated current)
When the inverter output current is within any positive or negative detection width of the current, the inverter
multi-function output terminal Terminal (function 28/29) outputs ON signal.
S3100A provides two sets of arbitrary current arrival and detection width parameters. Figure 5-24 is a schematic
diagram of the function.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...