123
11-32
Inverter status at the second
fault
The same to 11-17
~
11-24
11-33
Power-on time at the second
fault
11-34 Running time on second failure
11-37 Frequency at first failure
11-38 Current at first fault
11-39 Bus voltage at first fault
11-40
Input terminal status at the first
fault
11-41
Output terminal status at the
first fault
11-42 Inverter status at first fault
11-43 Power-on time at first failure
11-44 Operating time at first failure
11-47
Fault protection action selection1
Factory setting
0
Setting range
Single digit
Motor overload(OL1)
0
Coast to stop
1
Stop according to the stop mode
2
Continue to run
Tens digital
Input phase loss(SPI)(Same bit)
Hundreds
digital
Output phase loss(SPo)(Same bit)
Thousands
digital
External fault(EF)(Same bit)
Ten thousands
digital
Communication error(CE)(Same bit)
11-48
Fault protection action selection 2
Factory setting
0
Setting range
Single digit
Reserved
Tens digital
EEPROM read write fault
(EEP)
0
Coast to stop
1
Stop according to the stop mode
Hundreds
digital
Reserved
Thousands
digital
Reserved
Ten thousands
digital
Operating time arrival (Eond) (same as 11-47 digits)
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...