57
17 Torque control parameters
indicates that the parameters can be set during operation.
Parame
ter
Parameter function
Setting range
Factory
setting
17-06
Torque control reverse maximum
frequency
0.00Hz
~
Max frequency
50.00Hz
17-07
Torque control acceleration time
0.00s
~
65000s
0.00s
17-08
Torque control Deceleration time
0.00s
~
65000s
0.00s
22 Control optimization parameters
indicates that the parameters can be set during operation.
Parame
ter
Parameter function
Setting range
Factory
setting
22-00
DPWM switching upper limit
frequency
0.00Hz
~
Maximum operating frequency
8.00Hz
22-01
Reserved
22-02
Dead zone compensation mode
selection
0:No compensation
1:Compensation mode 1
1
22-03
Random PWM depth
0:Random PWM is invalid
1
~
10:Random depth of PWM carrier
frequency
0
22-04
Fast current limit enable
0:No enabling
1:Enabling
1
22-05
Current detection compensation
100
~
110
105
22-06
Undervoltage level
DC200V-DC420V
220V:200V
380V:350V
22-07
Reserved
22-08
Reserved
22-09
Overvoltage level
DC200V-DC820V
220V:400V
380V:820V
99 Monitoring parameters
indicates that the parameters can be set during operation.
Parame
ter
Parameter function
Setting range
99-00
Running frequency(Hz)
0.01Hz
99-01
Setting frequency(Hz)
0.01Hz
99-02
Bus voltage(V)
0.1V
99-03
Output voltage(V)
1V
99-04
Output current(A)
0.01A
99-05
Output power(kW)
0.1kW
99-06
Output torque(%)
0.1%
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...