RTU Frame format:
Frame header (START)
3.5 character time
Slave address (ADR)
Communication address:1~247
Command code (CMD)
03: Read slave parameters;
06: Write slave parameters
DATA(N-1)
Data content: Function code parameter address,
function code parameter number, function code
parameter value, etc.
DATA(N-2)
……
DATA 0
CRC CHK upper bite
Detection value: CRC value
CRC CHK lower bite
END
3.5 character time
Command code and communication data description:
Command code: 03H, read N words (Word can read up to 12 words)
For example: the start address 0002 of the inverter with slave address 01 is continuously reading two consecutive
values.
RTU host command information
RTU slave response information
ADR
01H
ADR
01H
CMD
03H
CMD
03H
Start address upper bit
00H
Byte number
04H
Start address lower bit
02H
Date address 0002H upper bit
00H
Date number upper bit
00H
Date address 0002H lower bit
00H
Date number lower bit
02H
Date address 0003H upper bit
00H
CRC CHK lower bit
CRC CHK
Date address 0003H lower bit
01H
CRC CHK upper bit
CRC CHK Lower bit
CRC CHK
CRC CHK Upper bit