94
Setting
value
Function
Description
37
Lower limit frequency reached
(also output when stopped)
When the running frequency reaches the lower limit frequency, the
ON signal is output. The signal is also ON in the stop state.
38
Warning output
When the inverter fails, and the fault handling mode is Continue to
run, the inverter warning output.
39
Reserved
Reserved
40
Current running time reached
When the inverter's current running time exceeds the time set in
09-53, it outputs an ON signal.
06-05
DFM terminal output mode selection
Factory setting
0
Setting range
0
Pulse output(DFM(P))
1
Switch output(DFM(M))
The DFM terminal is a programmable multiplex terminal, which can be used as a high-speed pulse output
terminal (DFM(P)) or an open collector switching output terminal (DFM(M)).
When DFM(P) is output as a pulse, please refer to 06-06 for DFM(P) related functions. The maximum frequency
of the output pulse is 100kHz.
When DFM(M) is output as a switch, please refer to 06-04 for DFM(M) related functions.
06-06
DFM(P) output function selection
Factory setting
0
06-07
AFM output function selection
Factory setting
0
06-08
Reserved
Factory setting
DFM (P) terminal output pulse frequency range is 0.01kHz ~ 06-09 (DFM (P) output maximum frequency), 06-09
can be set between 0.01kHz ~ 100.00kHz.
Analog output AFM output range is 0V ~ 10V. The relationship between the range of pulse output or analog output
and the scaling of corresponding functions is shown in the following table:
Setting value Funtion
Pulse or analog output 0.0%~100.0% corresponding function
0
Running frequency
0 to max output frequency
1
Set frequency
0 to max output frequency
2
Output current
0 to 2 times of motor rated current
3
Output torque
0 to 2 times of motor rated torque
4
Output power
0 to 2 times rated power
5
Output voltage
0 to 1.2 times of inverter rated voltage
6
PULSE input
0.01kHz
~
100.00kHz
7
AVI1
0V
~
10V
8
AVI2/ACI
0V
~
10V(or 0
~
20mA)
9
Reserved
10
Length
0 to maximum set length
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...