136
Sudden jump frequency amplitude: Sudden jump frequency = wobble amplitude AW × sudden jump frequency
amplitude (13-02). If the wobble amplitude is selected relative to the center frequency (13-00=0), the kick
frequency is the changing value. If the wobble amplitude is selected relative to the maximum frequency (13-00=1),
the kick frequency is a fixed value.
The operating frequency of the wobble frequency is constrained by the upper and lower frequency limits.
13-03
Wobble frequency cycle
Factory setting
10.0s
Setting range 0.1s
~
3000.0s
13-04
Wobble triangle wave rise time
Factory setting
50.0%
Setting range 0.1%
~
100.0%
Wobble cycle: the time value of a complete wobble cycle.
The triangular wave rise time (13-04) of the wobble frequency is the percentage of the triangular wave rise time
relative to the wobble period (13-03).
Triangle wave rise time=(13-03)×(13-04), the unit is second.
Triangle wave fall time=(13-03)×(1
-
(13-04)), the unit is second.
13-05
Set length
Factory setting
0m
Setting range 0m
~
65535m
13-06
Actual Length
Factory setting
0m
Setting range 0m
~
65535m
13-07
Pulses per meter
Factory setting
100.0
Setting range 0.1
~
6553.5
The above parameters are used for fixed length control.
The length information needs to be collected through the multifunctional digital input terminal. The number of
pulses sampled by the terminal is divided by 13-07 pulses per meter, and the actual length 13-06 can be
calculated. When the actual length is greater than the set length 13-05, the multi-function output terminal (function
10) outputs an ON signal.
During the fixed-length control, the length reset operation can be performed through the multi-function MI terminal
(MI function selection is 28). For details, please refer to 04-00~04-04.
In application, the corresponding multi-function input terminal function needs to be set to "length count input"
(function 27). When the pulse frequency is high, the MI5 port must be used.
13-08
Set count value
Factory setting
1000
Setting range 1
~
65535
13-09
Designated count value
Factory setting
1000
Setting range 1
~
65535
The count value needs to be collected through the multi-function digital input terminal. The application needs to
set the corresponding multi-function input terminal function to "counter input" (function 25). When the pulse
frequency is high, the MI5 port must be used.
When the count value reaches the set count value 13-08, the multi-function output terminal (function 8) outputs an
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...