102
Bit11
Reserved
Bit12
Count value
Bit13
Length
Bit14
Load speed
Bit15
PID setting
If the above parameters need to be displayed during operation, set the
corresponding position to 1, set the binary number to hexadecimal and set it to
08-03.
08-04
LED operation display parameter 2
Factory setting
0
Setting range
0000
~
FFFF
Bit00
PID feedback
Bit01
PLC stage
Bit02
PULSE input pulse frequency(kHz)
Bit03
Running frequency 2(Hz)
Bit04
Remaining running time
Bit05
AVI1 voltage Before correction(V)
Bit06
AVI2/ACI voltage Before correction(V)
Bit07
Reserved
Bit08
Line speed
Bit09
Current power-on time(Hour)
Bit10
Current running time(Min)
Bit11
PULSE Input pulse freuency(Hz)
Bit12
Communication setting value
Bit13
Reserved
Bit14
Main frequency X display (Hz)
Bit15
Auxiliary frequency Y display (Hz)
If the above parameters need to be displayed during operation, set the
corresponding position to 1, set the binary number to hexadecimal and set it to
08-04.
Running display parameters are used to set the parameters that can be viewed when the inverter is in running
state.
The maximum number of status parameters available for viewing is 32, and the status parameters to be displayed
are selected according to the binary bits of the 08-03 and 08-04 parameter values. The display order starts from
the lowest bit of 08-03.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...