01 Motor Control Parameters
01-00
The first motor control mode
Factory setting
0
Setting range
0
Speed sensorless vector control (SVC)
2
Vf control
0: Speed sensorless vector control
Refers to open-loop vector control, which is suitable for the usual high-performance control occasions. One
inverter can only drive one motor. Such as machine tools, centrifuges, wire drawing machines, injection
molding machines and other loads.
2: V/f control Applicable to the occasions where the load requirement is not high, or one inverter drives multiple
motors, such as fans and pumps. It can be used in a situation where one inverter drives multiple motors.
Tip: Motor vector parameter self-learning must be done when selecting vector control mode. Only accurate motor
parameters can take advantage of the vector control method. By adjusting the speed regulator parameter 02
group of parameters, you can get better performance.
01-01
Motor parameter self-learning
Factory setting
0
Setting range
0
No self-learning
1
Asynchronous motor static self-learning
2
Asynchronous motor complete self-learning
0: No self-learning.
1: Asynchronous motor static self-learning, suitable for occasions where asynchronous motor and load are not
easy to disconnect. Before static self-learning, the motor nameplate parameters 01-02~01-06 must be set
correctly. Asynchronous motor static self-learning,the inverter can obtain three parameters 01-07~01-09.
Action description: Set the function code to 1, and then press the RUN key, the inverter will perform static
self-learning.
2: Asynchronous motor complete self-learning
In order to ensure the dynamic control performance of the inverter, please select complete self-learning. At this
time, the motor must be disconnected from the load to keep the motor in a no-load state.
In the complete self-learning process, the inverter first performs static self-learning, and then accelerates to the
rated frequency of the motor according to the acceleration time 00-07 80%, after a period of time, decelerate to
stop according to the deceleration time 00-08 and end self-learning.
Before the complete self-learning of the asynchronous motor, in addition to the need to set the motor type and
motor nameplate parameters 01-02~01-06, after self-learning, the inverter can obtain five motor parameters
01-07~01-11, vector control PI parameters 02 -13~02-16.
Action description: Set the function code to 2, and then press the RUN key, the inverter will perform complete
self-learning.
01-02
Motor rated power
Factory setting
Type setting
Setting range 0.1kW
~
1000.0kW
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...