134
Description: Data read from 5000H compares with the actual fault as shown in the table below.
Inverter fault
addresss
DescriptionInverter fault information description
5000H
0000:No fault
0015:EEPROM read write error
0001:Short-circuit protection
0016:Inverter hardware fault
0002:Acceleration over current
0017:Motor short circuit to ground
0003:Deceleration over current
0018:Reserved
5000H
0004:Constant speed over current
0019:Reserved
0005:Acceleration overvoltage
001A:Running time arrival
0006:Deceleration overoltage
001B:Reserved
0007:Constant speed overvoltage
001C:Reserved
0008:Reserved
001D:Power-on time arrival
0009:Bus undervoltage fault
001E:Load failure
000A:Inverter overload
001F:The PID feedback disconnected
000B:Motor overload
0028:Wave-by-wave current limiting fault
000C:Input phase loss
0029: Switching motor fault during operation
000D:Output phase loss
002a: Excessive speed deviation
000E:Module overheat
002b: Motor over speed
000F:External fault
002d: Motor over temperature
0010:Communication error
005a: Encoder wire number setting error
0011:Contactor fault
005b: Encoder not connected
0012:Current detection fault
005C: Initial position error
0013:Motor self-learning error
005E: Speed feedback error
0014:Reserved
Communication error message response:
When a communication frame is detected as an error, the slave responds with a one-byte error code that defines
the cause of the error. After the main device application receives an error code response, the typical process is to
resend the message or make a command change for the corresponding error.
Communication error code definition:
Communication error home address
Wrong code definition
5001H
0000:No fault
0001:Password error
0002:Command code error
0003:CRC checking error
0004:Invalid address
0005:Invalid parameters
0006:Parameter change invalid
0007:System locked
0008:Being EEPROM operation
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...