76
03-11
V/f oscillation suppression gain
Factory setting
Type setting
Setting range 0
~
100
The selection method of the gain is as small as possible under the premise of effectively suppressing the
oscillation, so as to avoid adversely affecting the V/f operation. Select this gain to be 0 when there is no oscillation
in the motor. It is only necessary to increase the gain appropriately when the motor oscillates significantly.The
greater the gain, the more obvious the suppression of the oscillation.
When using the suppression oscillation function, the motor rated current Motor rated current and no-load current
parameters are required to be accurate,otherwise the V/f oscillation suppression effect is not good.
03-13
V/f separated voltage source
Factory setting
0
Setting range
0
Digital setting(03-14)
1
AVI1
2
AVI2/ACI
3
Reserved
4
PULSE setting (MI5)
5
Multi-step speed command
6
Simple PLC
7
PID
8
Communication setting
Note: 100.0% corresponds to the rated voltage of the motor
03-14
Voltage digital setting of V/f detached
Factory setting
0V
Setting range 0V
~
Motor rated voltage
V/f detach separation is generally used in applications such as induction heating, inverter power supply and
torque motor control.
If V/f separated control is selected, the output voltage can be set by parameter 03-14, or set communication can
be given by analog quantity, multi-step speed command, PLC, PID or communication. When a non-numeric
setting is selected, 100% of each setting corresponds to the rated voltage of the motor. When the percentage of
the output setting such as the analog quantity is negative, the set absolute value is used as the effective setting
value.
0.Digital setting (03-14)
Voltage is set by 03-14.
1.AVI1
2.AVI2/ACI
Voltage is confirmed by analog input terminal.
4.Pulse setting(MI5)
The voltage reference is given by the terminal pulse. Pulse given signal specifications: voltage range 20V ~ 27V,
frequency range 0kHz ~ 100kHz.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...