45
07 Start and stop control parameters
indicates that the parameters can be set during operation.
Parame
ter
Parameter function
Setting range
Factory
setting
07-00
Startup mode
0:
Direct start
1:
Rotation speed tracking restart
2:Pre-excitation start
3:Reserved
0
07-01
Startup frequency
0.00Hz
~
10.00Hz
0.00Hz
07-02
Startup frequency holding time
0.0s
~
100.0s
0.0s
07-03
Startup DC braking current /
pre-excitation current
0%
~
100%
0%
07-04
Startup DC braking time /
pre-excitation time
0.0s
~
100.0s
0.0s
07-05
Stop mode
0:
Decelerate to stop
1:
Coast to stop
0
07-06
Starting DC braking frequency at
stop
0.00Hz
~
max frequency
0.00Hz
07-07
DC braking waiting time at stop
0.0s
~
100.0s
0.0s
07-08
DC braking current at stop
0%
~
100%
50%
07-09
DC braking time at stop
0.0s
~
100.0s
0.0s
07-10
Brake usage
0%
~
100%
80%
07-11
Acceleration and deceleration
mode
0:linear acceleration / deceleration
1:S curve acceleration and deceleration A
2:S curve acceleration / deceleration B
0
07-12
S curve start time ratio
0.0%
~
(100.0%-07-13)
30.0%
07-13
S curve end time ratio
0.0%
~
(100.0%-07-12)
30.0%
07-14
Rotation speed tracking mode
0:Start from stop frequency
1:Start from zero speed
2:Start from maximum frequency
0
07-15
Rotation speed tracking speed
1
~
100
20
08 Man-machine interface parameters
indicates that the parameters can be set during operation.
Parame
ter
Parameter function
Setting range
Factory
setting
08-00
User password
0
~
65535
0
08-01
QUICK/JOG key function
selection
0:QUICK/JOG invalid
1:
Keyboard command channel and remote
command channel (terminal Terminal
command channel or communication
command channel) switch
2:Forward and reverse switching
3:
Forward jog
4:
Reverse jog
5:Reserved
3
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...