81
K4
K3
K2
K1
Command setting
Corresponding
parameters
OFF
OFF
OFF
ON
Multi-step speed command 1
05-01
OFF
OFF
ON
OFF
Multi-step speed command 2
05-02
OFF
OFF
ON
ON
Multi-step speed command 3
05-03
OFF
ON
OFF
OFF
Multi-step speed command 4
05-04
OFF
ON
OFF
ON
Multi-step speed command 5
05-05
OFF
ON
ON
OFF
Multi-step speed command 6
05-06
OFF
ON
ON
ON
Multi-step speed command 7
05-07
ON
OFF
OFF
OFF
Multi-step speed command 8
05-08
ON
OFF
OFF
ON
Multi-step speed command 9
05-09
ON
OFF
ON
OFF
Multi-step speed command 10
05-10
ON
OFF
ON
ON
Multi-step speed command 11
05-11
ON
ON
OFF
OFF
Multi-step speed command 12
05-12
ON
ON
OFF
ON
Multi-step speed command 13
05-13
ON
ON
ON
OFF
Multi-step speed command 14
05-14
ON
ON
ON
ON
Multi-step speed command 15
05-15
When the frequency source is selected as multi-step speed, the parameters 100.0% of 05-00~05-15 correspond
to the maximum frequency max frequency 00-03. Multi-step speed command can not only be used as a multi-step
speed function, but also can be used as a given source of PID, or as a voltage source for V/f separation control to
meet the needs of switching between different given values.
Attached Table 2 Acceleration and deceleration time terminal function description
Terminal 2
Terminal 1
Acceleration or deceleration time selection
Corresponding parameters
OFF
OFF
Acceleration time 1
00-07,00-08
OFF
ON
Acceleration time 2
09-03,09-04
ON
OFF
Acceleration time 3
09-05,09-06
ON
ON
Acceleration time 4
09-07,09-08
04-08
MI Filter time
Factory setting
0.010s
Setting range 0.000s
~
1.000s
Set the software filtering time for the terminal state of the MI terminal. If the input terminal of the application
occasion is susceptible to interference and cause malfunctions, this parameter can be increased to enhance the
anti-interference ability. However, the increase of the filtering time will cause the response of the MI terminal to
become slow.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...