06 Output Terminal Parameters
S3100A series inverters are equipped with a multi-function analog output terminal Terminal, a multi-function
digital output terminal Terminal, a multi-function relay output terminal Terminal, a DFM terminal Terminal (can be
used as high-speed pulse output terminal Terminal, also can be used as an open collector switch output).
06-00
MO1 output function selection
Factory setting
1
06-01
Control board relay function selection(RA-RB-RC)
Factory setting
2
06-02
Reserved
Factory setting
06-03
Reserved
Factory setting
06-04
DFM(M) output function selection
Factory setting
0
The function descriptions of the multi-function output terminals are as follows:
Setting
value
Function
Description
0
No output
Output terminal is invalid
1
Inverter is running
Indicates that the inverter is in running state and has an output
frequency (which can be zero), at this time it outputs an ON signal
2
Fault output (stop)
When the inverter is faulty and the fault is stopped, the ON signal is
output.
3
Frequency level detection
FDT1 output
Please refer to the parameters 09-19,09-20
4
Frequency reached
Please refer to the parameters 09-21
5
Running at zero speed
(No output when stopped)
When the inverter is running and the output frequency is 0, the ON
signal is output. When the inverter is stopped, this signal is OFF.
6
Motor overload pre-alarm
Before the overload protection action of the motor, the judgment is
based on the threshold value of the overload pre-alarm, and the ON
signal is output after the pre-alarm threshold is exceeded. Refer to
parameters 11-00
~
11-02 for motor overload parameter setting.
7
Inverter overload pre-alarm
10s before the inverter overload protection occurs, output ON
signal.
8
Set count value reached
When the count value reaches the value set in 13-08, the ON signal
is output.
9
Designated count value
reached
When the count value C reaches the value set in 13-09, the ON
signal is output. For counting function, please refer to 13 groups of
function description
10
Length reached
When the detected actual length exceeds the length set by 13-05,
the ON signal is output.
11
PLC cycle completed
When the simple PLC completes one cycle of operation, it outputs a
pulse signal with a width of 250ms.
12
Cumulative running time
arrived
When the cumulative running time of the inverter exceeds the time
set in 09-17, it outputs an ON signal.
13
Frequency limited
When the set frequency exceeds the upper limit frequency or lower
limit frequency, and the output frequency of the inverter reaches the
upper limit frequency or lower limit frequency, an ON signal is
output.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...