120
10-26
PID feedback lower limit detection
Factory setting
0.0%
Setting range
0.0%: No judgment
0.1%
~
100.0%
10-27
PID feedback loss detection time
Factory setting
0.0s
Setting range 0.0s
~
20.0s
This parameter can detect whether the PID feedback line is missing.
When the PID feedback amount is less than the feedback loss detection value 10-26, and the duration exceeds
the PID feedback loss detection time 10-27, the inverter alarms the fault PIDE, and handles it according to the
selected fault handling method.
10-28
PID Shutdown calculation
Factory setting
0
Setting range
0
No operation during shutdown
1
Operation at shutdown
It is used to select whether PID continues to operate under PID stop status. In general applications, PID should
stop calculation in the stop state.
11 Fault and Protection Parameters
11-00
Motor overload protection selection
Factory setting
1
Setting range
0
Disabled
1
Enabled
11-01
Motor overload protection gain
Factory setting
1
Setting range 0.20
~
10.00
0: No protection, no motor overload protection feature (use with caution), at this time, the inverter has no overload
protection for the load motor.
1: At this time, the inverter judges whether the motor is overloaded according to the inverse time limit curve of the
motor overload protection. The inverse time limit curve of motor overload protection is: 220%×(11-01)×motor
rated current, which will alarm the motor overload fault for 1 minute; 150%×(11-01)×motor rated current, which
lasts 60 minutes Then alarm motor overload.
The user sets the value of 11-01 according to the actual overload capacity of the motor. If the setting is too large,
the motor may be damaged due to overheating and the inverter may not alarm in time!
11-02
Motor overload pre-warning coefficient
Factory setting
80%
Setting range 50%
~
100%
This function is used to output an early warning signal to the control system through the multi-function output
terminal before the motor overload protection. The early warning function can set how much early warning is
given before the motor overload protection. The larger the value,the smaller the early warning advance.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...