67
4: Switch between auxiliary frequency source Y and main and auxiliary calculation results When multi-function
input terminal function 18 (frequency switching) is invalid, auxiliary frequency Y is used as the target frequency.
When the multi-function input terminal function 18 (frequency switching) is valid, the main and auxiliary
calculation results are used as the target frequency.
Tens: Main and auxiliary calculation relationship of frequency source:
0: Main frequency source X + auxiliary frequency source Y
The sum of the main frequency X and the auxiliary frequency Y is taken as the target frequency. Realize the given
function of frequency superposition.
1: Main frequency source X- auxiliary frequency source Y
The difference between the main frequency X and the auxiliary frequency Y is taken as the target frequency.
2: MAX (main frequency source X, auxiliary frequency source Y) Take the maximum absolute value of the main
frequency X and auxiliary frequency Y as the target frequency.
3: MIN (main frequency source X, auxiliary frequency source Y) Take the minimum absolute value of the main
frequency X and auxiliary frequency Y as the target frequency. In addition, when the frequency source is selected
as the main and auxiliary operations, the offset frequency can be set through 00-19, and the offset frequency is
superimposed on the main and auxiliary operation results to flexibly respond to various needs.
00-19
Auxiliary frequency source offset frequency when
superimposed
Factory setting
0.00Hz
Setting range 0.00Hz
~
max frequency 00-03
This parameter is only valid when the frequency source is selected as the main and auxiliary operation.
When the frequency source is the main and auxiliary operation, 00-19 is used as the offset frequency, and the
result of the main and auxiliary operation is superimposed as the final frequency setting value, and the frequency
setting is more flexible.
00-20
Upper frequency source
Factory setting
0
Setting range
0
00-04
setting
1
AVI1
2
AVI2/ACI
3
Reserved
4
Pulse setting
5
Communication setting
Source selection for upper frequency.Especially in torque control, the output frequency of the inverter can be
changed by changing the upper limit frequency.
Note: 100% of the analog input setting corresponds to 00-04.
00-21
Upper frequency offset
Factory setting
0.00Hz
Setting range 0.00Hz
~
max frequency 00-03
When the upper limit frequency is set by analog or PULSE, 00-21 is used as the offset value of the set value, and
the offset frequency is superimposed on the set upper limit frequency value of 00-20 as the final set value of the
upper limit frequency.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...