125
11-59
Instantaneous power failure action selection
Factory setting
0
Setting range
0
Invalid
1
Deceleration
2
Decelerate to stop
11-60
Instantaneous power failure action pause judgment
voltage
Factory setting
85%
Setting range 80
~
100%
11-61
Judgment time of instantaneous power failure voltage rise
Factory setting
0.5s
Setting range 0.0s
~
100.0s
11-62
Judgment voltage of instantaneous power failure
Factory setting
80%
Setting range 60%
~
100%(Standard bus Voltage)
Refers to the moment when there is a power failure or the voltage drops suddenly, the inverter reduces the output
speed, so that the load feedback energy maintains the inverter DC bus voltage, so that the inverter continues to
run.
If 11-59=1, the inverter decelerates when there is an instantaneous power failure or a sudden drop in voltage, and
when the bus voltage returns to normal, the inverter normally accelerates to the set frequency. The basis for
judging the return of the bus voltage to normal is that the bus voltage is normal and the duration exceeds the set
time of 11-61.
If 11-59=2, during an instantaneous power failure or a sudden drop in voltage, the inverter decelerates until it
stops.
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...
Page 24: ...20 Size 5 Unit mm S3100A 4T45G 55P 4T110G Size 6 Unit mm S3100A 4T110G 132P 4T160G 185P ...
Page 25: ...21 Size 7 Unit mm S3100A 4T185G 200P 4T220G Size 8 Unit mm S3100A 4T220G 250P 4T315G ...
Page 26: ...22 Size 9 Unit mm S3100A 4T315G 355P 4T400G 450P Size 10 Unit mm S3100A 4T450G 500P 4T500G ...