PROGRAMMING GUIDE
SINUS PENTA
71
/
486
M101 Connection Status
M101
Range
Bit-controlled measure
Active
This measure is active only if programmed from parameter
R021
.
Address
1338
Function
Status of the connections supported by ES851. Note that the COM1 serial link is RS232 by
default, whereas COM 2 is RS485 by default.
For more details, please refer to the Programming Guide manual for the Data Logger
ES851.
Table 9: Data Logger connection status
Bit n.
Connection
Description
0-7
Type of modem connection failure
0: None
1: Dial KO
2: Connect KO
3: Authentication KO
4: IPCP KO*
5: Modem not yet initialized
6: Modem init KO
7: Modem not configured
8: Modem not dial out
16: Connect end (echo time out)
32: Connect end (idle time out)
64: Connect end (term expired)
8-10
Status of the connection via modem
0: No conn.
1: Dialing
2: Connecting
4: Connected
5: Attempt finished
11
COM1
0: No data exchange
1: Data exchanged
12
COM2
0: No data exchange
1: Data exchanged
13
Ethernet
0: No connection
1: Connection
14-15
Reserved
* In computer networking, the
Internet Protocol Control Protocol (IPCP)
is a network control protocol for establishing
and configuring Internet Protocol over a Point-to-Point Protocol link. The IPCP configures, enables, and disables the IP
protocol modules on both ends of the point-to-point link.