8.9.
Data Logger Measures Menu
This menu displays the status of the types of connections (serial links, Ethernet and modem) supported by ES851 Data
Logger board.
This menu can be viewed only if the Data Logger board is fitted.
See also the DATA LOGGER MENU.
M100 Data Logger Status (Line 3)
M100
Line 3
Range
0
÷
2
0: NOT FITTED
1: OK not interlocked
2: OK interlocked
Active
This measure is active only if programmed from parameter
R021
.
Address
1336
Function
0: NOT FITTED
, ES851 is not installed on the Penta drive.
1: OK not interlocked
, ES851 is operating independently of the drive where it is installed.
To program ES851, a connection to a computer via the RemoteDrive software is required, or
a special preset set via display/keypad is required (see the DATA LOGGER MENU).
2: OK interlocked
, ES851 is ready to be configured even through the display/keypad of the
drive where it is installed.
M100 ES851 Fault (Line 4)
M100
Line 4
Range
0
÷
6, 99
÷
104
0: No alarm
1: Parameter save fault
2: Log write error
3: FBS configuration failure
4: RS232 Modbus configuration failure
5: RS485 Modbus configuration failure
6: TCP/IP stack configuration failure
99: Flash card lacking or inaccessible
100: Invalid stream access
101: TCP/IP socket fault
102: Dial out connection failure
103: Control board clock failure
104: Modem initialization failure
Active
This measure is active only if programmed from parameter
R021
.
Address
1340
Function
This indicates a general alarm tripped for ES851. In case an alarm trips, please contact
ELETTRONICA SANTERNO’s CUSTOMER SERVICE and mention the alarm code and
name.