PROGRAMMING GUIDE
SINUS PENTA
267
/
486
Table 76: IFD control parameters for the connected motors
Parameter
Motor 1
Motor 2
Motor 3
Rated frequency:
Rated frequency of the connected motor (current rating).
C015
C058
C101
Rated voltage:
rated voltage of the connected motor (voltage rating).
C019
C062
C105
V/f curve type:
Type of V/f curve applied.
C013
C056
C099
Torque reduction with quadratic curve:
Torque reduction using V/f quadratic curve.
C032
C075
C118
Rated speed referring to torque reduction with quadratic curve:
Speed actuating the torque reduction using a quadratic curve.
C033
C076
C119
Voltage preboost:
Determines the voltage produced by the drive at min. output frequency
fomin.
C034
C077
C120
Voltage Boost 0:
Determines the voltage variations in respect to the nominal voltage at the
frequency set up by the relevant parameter.
C035
C078
C121
Boost 0 application frequency:
Determines the Boost 0 application frequency.
C035a
C078a
C121a
Voltage Boost 1:
Determines the frequency for the application of the boost at preset
frequency.
C036
C079
C122
Boost 1 application frequency:
Determines the Boost 1 application frequency at preset frequency.
C037
C080
C123
Autoboost:
Variable torque compensation expressed as a percentage of the rated
motor voltage. The preset value expresses the voltage increase when the
motor is running at rated torque.
C038
C081
C124
34.1.5.
E
X AMPLE
1
-
V/
F
P
AT T ERN
P
ARAMET ERIZAT ION
Motor 1: the voltage/frequency pattern is to be programmed for an asynchronous motor (400V/50Hz) with a rated speed
of 1500rpm up to 2000rpm.
Type of V/f curve
C013
=
Constant Torque
Rated frequency
C015
=
50 Hz
Rated motor rpm
C016
=
1500rpm
Rated voltage
C019
=
400 V
Preboost
C034
=
depending on the starting torque
Max. speed
C029
=
2000rpm