PROGRAMMING GUIDE
SINUS PENTA
327/486
Parameter
FUNCTION
User Level
MODBUS
Address
Default
Values
C184a
Disable external torque limit during fluxing
ENGINEERING
1200
No
C185
Stop Mode
ADVANCED
1185
deceleration ramp
C186
Fire Mode enabling Input
ENGINEERING
1186
None
C187
Torque Limit Source Ref. Disabling Input
ADVANCED
1187
none
C187a
Multitorque 0 Input
ADVANCED
1094
None
C187b
Multitorque 1 Input
ADVANCED
1095
None
C188a
PID Multireference 1 Input
ENGINEERING
1365
none
C188b
PID Multireference 2 Input
ENGINEERING
1366
none
C188c
PID Multireference 3 Input
ENGINEERING
1367
none
NOTE
If a parameter is set to zero, its function is disabled, otherwise the parameter value stands
for the MDIx input assigned to the function.
NOTE
Auxiliary digital inputs XMDI (values from 17 to 24 in control function parameters) can be
set up only after setting XMDI/O in parameter
R023
.
CAUTION
Set
C182=1
to allocate 2 functions to the same terminal
.
I006 Function Selection for MDI Control
I006
Range
0
÷
2
0
→
Inactive
1
→
Clear all
2
→
Set factory default
Default
This is not a programming parameter: the input is set to zero whenever the drive is
powered on and whenever the command is executed.
Level
ADVANCED
Address
1393
Function
0
→
Inactive.
1
→
Forces to “0
→
Inactive” the settings of all the digital inputs.
2
→
Forces to the default values the settings of all the digital inputs.
C149 START Input
C149
Range
0
÷
16
0
÷
24 if ES847 or ES870 is fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
1
MDI1
Level
ADVANCED
Address
1149
Function
When the
START
input is
activated
(the
ENABLE-A
and
ENABLE-B
inputs are
activated as well),
RUN
is enabled: the speed (torque)
setpoint
increases following
the programmed ramp until it reaches the active
reference
. In IFD control mode, the
main speed reference shall be other than zero for
RUN
enable.
When the
START
input is
inactive
(even if the
ENABLE-A
and
ENABLE-B
inputs
are activated)
RUN
is disabled: the reference is set to zero and the speed (torque)
setpoint
drops to zero based on the programmed deceleration ramp.
NOTE
If the PROFIdrive option is present, parameter
C149 START Input
must be assigned to value
1: MDI1.