P060 Type of Signal over AIN2 Input
P060
Range
0
÷
4
0:
±
10 V
1:
±
20 mA
2: 4
÷
20 mA
3: 0
÷
10 V
4: 0
÷
20 mA
Default
2
2: 4
÷
20 mA
Level
ADVANCED
Address
660
Function
This parameter selects the type of differential analog signal over terminals
AIN2+
and
AIN2–
in the terminal board.
The signal can be a voltage signal, a current signal, a unipolar signal, or a bipolar
signal.
0:
±
10 V
Bipolar voltage input between –10V and +10V. The detected signal is
saturated between these two values.
1
:
±
20 mA Bipolar current input between –20mA and +20mA. The detected signal is
saturated between these two values.
2
: 4
÷
20 mA Unipolar current input with min. threshold, b4 mA and +20mA.
The detected signal is saturated between these two values.
Before being saturated, if the detected signal is lower than 4 mA or greater than 20
mA, alarms
A068
or
A104
trip.
3
: 0
÷
10 V Unipolar voltage input between 0V and +10V. The detected signal is
saturated between these two values.
4
: 0
÷
20 mA Unipolar current input b0 mA and +20mA. The detected signal
is saturated between these two values.
NOTE
The value set in parameter
P060
must match with the status of switches
SW1–3, SW1-4
and
SW1-5
allowing selecting the proper electric circuit for the analog signal processing
(voltage signal or current signal).
NOTE
If the PTC thermal protection (
C274
) is enabled, the reference from
AIN2
is
automatically managed as a 0
÷
10V input. The only parameter enabled for the control of
AIN2 is
P064
;
P060, P061, P061a, P062, P062a
and
P063
cannot be viewed and are
not considered for calculations.
P061 Value of AIN2 Input Producing Min. Reference (X-axis)
P061
Range
–100
÷
100, if
P060
= 0
–200
÷
200, if
P060
= 1
+40
÷
200, if
P060
= 2
0
÷
100, if
P060
= 3
0
÷
200, if
P060
= 4
–10.0 V
÷
10.0 V, if
P060=
0:
±
10 V
–20.0 mA
÷
20.0 mA, if
P060
= 1:
±
20 mA
+4.0mA
÷
20.0 mA, if
P060
= 2: 4
÷
20 mA
0.0 V
÷
10.0V, if
P060
= 3: 0
÷
10 V
0.0 mA
÷
20.0 mA , if
P060
= 4: 0
÷
20 mA
Default
40
4.0mA
Level
ADVANCED
Address
661
Function
This parameter selects the value for AIN2 input signal for minimum reference, or
better the reference set in
C028xP061a
(Master mode) or in
C047xP061a
(Slave
mode). If motor 2 is active,
C071
and
C090
will be used instead of
C028
and
C047
; if
motor 3 is active, the values set in
C114
and
C133
will be used.