PROGRAMMING GUIDE
SINUS PENTA
223
/
486
P324 Channel 3: Measure Mode
P324
Range
0
÷
1
0: no input
1: val PT100
Default
0
0: no input
Level
ADVANCED
Address
924
Function
This parameter selects the type of analog signal available in terminals 31–32 in
ES847 expansion board.
0:
no signal is used. The P parameter relating to the analog input disappears.
1
: val PT100. The acquired signal is transformed into degrees centigrade.
See Measure
M071.
P325 Channel 3: Measure Offset
P325
Range
–30000 ÷ 30000
–300.00 ÷ 300.00
Default
0
0.0 °C
Level
ADVANCED
Address
925
Function
Value of the measure offset for channel 3: an offset can be applied to the
measure to correct possible errors.
P326 Channel 4: Measure Mode
P326
Range
0
÷
1
0: no input
1: val PT100
Default
0
0: no input
Level
ADVANCED
Address
926
Function
This parameter selects the type of analog signal available in terminals 33–34 in
ES847 expansion board.
0:
no signal is used. The P parameter relating to the analog input disappears.
1
: val PT100. The acquired signal is transformed into degrees centigrade.
See Measure
M072.
P327 Channel 4: Measure Offset
P327
Range
–30000 ÷ 30000
–300.00 ÷ 300.00
Default
0
0.0 °C
Level
ADVANCED
Address
927
Function
Value of the measure offset for channel 4: an offset can be applied to the
measure to correct possible errors.