PROGRAMMING GUIDE
SINUS PENTA
247
/
486
P380 MPL4: Testing Variable A
P380
Range
0
÷
7
0: >
1:
≥
2: <
3: ≤
4: ABS(x) >
5: ABS(x) ≥
6: ABS(x) <
7: ABS(x) ≤
Default
0
0: >
Level
ADVANCED
Address
980
Function
This parameter defines the test to be performed for the variable detected by
P378
using
P382
as a comparing value
.
P381 MPL4: Testing Variable B
P381
Range
0
÷
7
0: >
1: ≥
2: <
3: ≤
4: ABS(x) >
5: ABS(x) ≥
6: ABS(x) <
7: ABS(x) ≤
Default
0
0: >
Level
ADVANCED
Address
981
Function
This parameter defines the test to be performed for the variable detected by
P379
using
P383
as a comparing value.
P382 MPL4: Comparing Value for Test A
P382
Range
–32000
÷
32000
–320.00 %
÷
320.00 %
% of the full-scale value of selected variable A
, see Table
Default
0
0
Level
ADVANCED
Address
982
Function
This parameter defines the comparing value with the selected variable for test A.
P383 MPL4: Comparing Value for Test B
P383
Range
–32000
÷
32000
–320.00 %
÷
320.00 %
% of the full-scale value of selected variable B
, see Table
Default
0
0
Level
ADVANCED
Address
983
Function
This parameter defines the comparing value with the selected variable for test B.