SINUS PENTA
PROGRAMMING GUIDE
458
/
486
A052 Illegal XMDI in DGO
A052
Description
Illegal configuration of XMDI in the Digital Outputs menu.
Event
•
The drive checked if at least one XMDI input from ES847 or ES870 I/O
optional board is available in the DIGITAL INPUTS MENU;
•
The drive checked if
R023
(I/O Board setting) is set to 0 in the
EXPANSION BOARD CONFIGURATION MENU
Possible
cause
Wrong settings.
Solution
Check settings and enter correct settings.
A053 Not PWONA
A053
Description
Hardware failure; IGBT A power on failure.
Event
IGBT A power on controlled by Motorola microcontroller has failed.
Possible
cause
Control board failure.
Solution
1. Reset the alarm: send a
RESET
command.
2. If the alarm persists, please contact ELETTRONICA SANTERNO’s Customer
Service.
A054 Optional Board not in
A054
Description
ES847 or ES870 not in.
Event
The control board detects no ES847 or ES870 I/O expansion boards after
parameter
R023
(I/O Board Setting) is set as
≠
0.
Possible
cause
Optional board not in or faulty.
Solution
1. Check consistency of parameter
R023
(see the EXPANSION BOARD
2. Reset the alarm: send a
RESET
command.
3. If the alarm persists, please contact ELETTRONICA SANTERNO’s Customer
Service.
A055 PTC Alarm
A055
Description
External PTC resistor tripped.
Event
The drive detected the opening of the PTC connected to
AIN2
input (R > 3600
ohm)
Possible
cause
•
Opening of the PTC due to motor overheating.
•
Incorrect wiring of PTC.
•
Incorrect setting of
SW1
hardware switch on the control board (see Installation
Solution
1. Allow the motor to cool, then reset the alarm.
2. Make sure that the PTC is correctly connected to
AIN2
analog input (see
3. Make sure that
SW1
hardware switch is correctly set.