SINUS PENTA
PROGRAMMING GUIDE
346
/
486
C181 Safety Start
C181
Range
0
÷
1
Inactive, Active
Default
0
Inactive
Level
ADVANCED
Address
1181
Function
This function
enables
the
Safety
START mode.
When this function is enabled and the drive is to be restarted after resetting an alarm,
open and close the
ENABLE-A
and
ENABLE-B
terminals.
This prevents the drive from RUNNING when it is turned off and on again (for example
after a mains loss) and the
START
and
ENABLE-A
and
ENABLE-B
inputs are on.
NOTE
If multiple terminal boards are selected with parameters
C140
,
C141
,
C142
, open and close
the
MDI2
terminals in one of the active terminal boards to restart the drive.
C182 Multiprogramming Enable
C182
Range
0
÷
1
Inactive, Active
Default
1
Inactive
Level
ENGINEERING
Address
1182
Function
This function allows allocating two different functions to the same terminal.
NOTE
Only few preset combinations are allowed.
When invalid configurations are set up, “ILLEGAL DATA” appears on the display/keypad of
the Penta drive.
C183 Max. Fluxing Time Before Drive Disable
C183
Range
0
÷
65000
0
÷
65000 ms
Default
0
Disabled
Level
ADVANCED
Address
1183
Control
VTC and FOC
Function
This function disables the drive if the fluxing time period is longer than the preset time (if
the
ENABLE
function, not a
START
command, is active).
To restore motor fluxing, disable and enable the
ENABLE
function, or if with the active
ENABLE
function a
START
command is also activated.
NOTE
The time set in C183 is added to the Fluxing Ramp Time set in
C041
/
C084
/
C127
.
C184 Fluxing at Activation only with START Closed
C184
Range
0 ÷1
0:No - 1:Yes
Default
0
0:No
Level
ADVANCED
Address
1184
Control
VTC and FOC
Function
Fluxing may be carried out only when the
START
command is closed.