PROGRAMMING GUIDE
SINUS PENTA
209/486
P286 MDO2: Function Applied to the Result of the 2 Tests
P286
Range
0
÷
12
0: (A) OR (B)
1: (A) SET (B) RESET
2: (A) AND (B)
3: (A) XOR (B)
4: (A) NOR (B)
5: (A) NAND (B)
6: (A\) OR (B)
7: (A) OR (B\)
8: (A\) AND (B)
9: (A) AND (B\)
10: (A) RESET (B) SET RISING EDGE
11: (A) SET (B) RESET FALLING EDGE
12: (A) RESET (B) SET FALLING EDGE
Default
1
1: (A) SET (B) RESET
Level
ADVANCED
Address
886
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value
.
P286a MDO2: Selecting Variable C
P286a
Range
0
÷
79
Default
0
D0: Disable
Level
ADVANCED
Address
644
Function
This parameter selects the digital signal used to calculate the value of
MDO2
digital output.
The digital signals that can be selected are given in Table 48.
P286b MDO2: Function Applied to the Result of f(A,B) C
P286b
Range
0
÷
12
0: f(A,B) OR (C)
1: f(A,B) SET (C) RESET RISING EDGE
2: f(A,B) AND (C)
3: f(A,B) XOR (C)
4: f(A,B) NOR (C)
5: f(A,B) NAND (C)
6: f(A,B)\ OR (C)
7: f(A,B) OR (C\)
8: f(A,B)\ AND (C)
9: f(A,B) AND (C\)
10: f(A,B) RESET (C) SET RISING EDGE
11: f(A,B) SET (C) RESET FALLING EDGE
12: f(A,B) RESET (C) SET FALLING EDGE
Default
1
1: (A) SET (B) RESET
Level
ADVANCED
Address
645
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value
.