PROGRAMMING GUIDE
SINUS PENTA
461/486
A065 Autotune KO
A065
Description
Autotune failed.
Event
Autotune aborted or failed.
Possible
cause
•
The
ENABLE
contact was disabled before autotune was over.
•
Autotune aborted, maybe because the parameter values were inconsistent with
the motor ratings.
Solution
1. Reset the alarm: send a
RESET
command.
2. Check the motor parameters and make sure that they are consistent with the
motor ratings (see the MOTOR CONFIGURATION MENU) and perform a new
autotune procedure.
3. If the alarm persists, please contact ELETTRONICA SANTERNO’s Customer
Service.
A066, A067, A068, A069 Current input < 4mA
A066 (REF)
A067 (AIN1)
A068 (AIN2)
A069 (XAIN5)
Description
A066
: REF Current input (4
÷
20mA) lower than 4mA
A067
: AIN1 Current input (4
÷
20mA) lower than 4mA
A068
: AIN2 Current input (4
÷
20mA) lower than 4mA
A069:
XAIN5 current input (4
÷
20mA) lower than 4mA
Event
A current value lower than 4 mA has been detected over one input (REF, AIN1,
AIN2, XAIN5) set with the following range: 4
÷
20mA.
Possible
cause
•
Wrong setting of
SW1
on the control board (except for
A069
).
•
Signal cable disconnected.
•
Failure in the current signal source.
Solution
1. Check setting of
SW1
(except for
A069
).
2. Check that the signal cable is properly connected to its terminal.
3. Check the current signal source.
NOTE
The alarms above trip only if the relevant inputs have been selected (see CONTROL
METHOD MENU and PID CONFIGURATION MENU).