C187a,C187b Multitorque Inputs
C187a
C187b
Range
0
÷
16
0
÷
24 if ES847 or ES870 is fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1094, 1095
Function
This function allows generating max. 3 torque limits that can be programmed via
parameters
P101÷P103
.
These 2 functions determine which of the 3 torque limits is active: the active value (
1
) or
inactive value (
0
) of each programmed input signal determines a bit-controlled binary
number, where
MULTITORQUE 0
is the least significant bit (bit 0).
If one of the two functions is not programmed, the relevant bit value is zero.
Table 107: Multitorque selection
Selected Multitorque =
Bit 1
Bit 0
MULTITORQUE 1
MULTITORQUE 0
Table 108: Selected Multitorque reference
Function:
Status of the
relevant input
MULTITORQUE
0
0
1
0
1
MULTITORQUE
1
0
0
1
1
Selected
Multitorque
0
1
2
3
Resulting
multitorque limit
(*)
P
101
P
102
P
103
(*) If both Multitorque inputs are inactive, the torque limit applied is the one that would be present if no Multitorque inputs
were active, such as:
•
If
C147
≠ 0, the limit coming from the source set in
C147
;
•
If
C147
= 0, the limit defined by
C047
,
C048
(see LIMITS MENU).
When switching between the two Multitorque modes, the ramps defined by parameters
P026
,
P027
(see RAMPS
MENU).
The activation of the input programmed in
C187
(if any) disables the torque limit forced by
C187a
,
C187
as follows:
•
If both Multitorque inputs are OFF, the limit set by
C047
,
C048
is forced without applying any ramps.
•
If at least one of the Multitorque inputs is ON, the limit set by
C047
,
C048
is forced by applying the ramp in
P026
.
•
When the input set in
C187
is disabled, the limits set in
P101
÷
P103
are applied following the ramps in
P026
,
P027
.