SINUS PENTA
PROGRAMMING GUIDE
398
/
486
C285 (C286,C287) Selection of PID Reference n. 1 ( 2, 3)
C285 (C286, C287)
Range
0
÷
10
0
÷
12 if ES847 is fitted
0: Disable
1: REF
2: AIN1
3: AIN2/PTC
4: Pulse Input
5: Serial Link
6: Fieldbus
7: Keypad
8: Encoder
9: V out
10: Up Down from MDI
11: XAIN4
12: XAIN5
Default
C285
= 2
C286
= 0
C287
= 0
C285
= 2: AIN1
C286
= 0
C287
= 0
Level
ENGINEERING
Address
1285 (1286, 1287)
Function
C285
selects the first PID reference source from the PID regulator. Up to three
reference sources may be configured
(285 – C287)
considered as a sum.
The sources are used by the PID and are expressed in percentage values (with
reference to their max. value and min. value set in the References menu).
If multiple reference sources are selected, their sum is considered. They are
saturated between
P246
and
P245
(PID reference maximum and minimum
value respectively).
Source 9 (V out) is useful when
C294
= 3: Voltage Sum. This is the output
voltage in IFD control with no PID corrections.
Reference sources 11 and 12 can be selected only after setting
XAIN
in
parameter
R023
.