PROGRAMMING GUIDE
SINUS PENTA
315
/
486
36.3.
List of Parameters C140 to C148
Table 94: List of parameters C140 to C148
Parameter
FUNCTION
User Level
MODBUS
Address
Default
Values
C140
Command digital input 1
ADVANCED
1140
1:Terminal Board
C141
Command digital input 2
ADVANCED
1141
1:Terminal Board
C142
Command digital input 3
ENGINEERING
1142
0
C143
Input reference 1
ADVANCED
1143
1: REF
C144
Input reference 2
ADVANCED
1144
2: AIN1
C145
Input reference 3
ENGINEERING
1145
0
C146
Input reference 4
ENGINEERING
1146
0
C147
Torque Limit input
ENGINEERING
1147
0
C148
Switch over from
Remote to Local command
ENGINEERING
1148
0: StandBy or Fluxing
NOTE
The programming range of parameters
C140
,
C141
,
C142
depends on the setting of
parameter
C150
and vice versa (see the detailed description of the parameters above).
C140 (C141, C142) Command Source Selection 1 (2, 3)
C140 (C141, C142)
Range
0
÷
5
0: Disabled,
1: Terminal Board,
2: Serial Link,
3: Fieldbus,
4: Terminal Board B,
5: Keypad
Default
C140
÷
C141
= 1
C142
= 0
C140
÷
C141
= 1: Terminal Board
C142
= 0: Disabled
Level
C140
÷
C141
ADVANCED;
C142
ENGINEERING
Address
1140 (1141,1142)
Function
Selection of the drive command source.
NOTE
Setting one of the three command sources to 5: Keypad and one or more of the other
command sources to different values from 5: Keypad is made possible only if:
1. STOP or STOP B digital inputs are set up (
C150
≠ 0 or
C150a
≠ 0) to enable
using the pushbuttons or
2. the source selection function is selected (
C179
≠ 0).
NOTE
If the digital input for source selection or command selection (parameter
C179
and
C179a
in the Digital Inputs Menu) is set to a value other than 0: Disabled, parameter
C142
(Command Source Selection 3) is always considered as OR bit by bit to the
selected source. The ENABLE input (MDI2), however, is considered as AND to the
selected source.