SINUS PENTA
PROGRAMMING GUIDE
332
/
486
DANGER!!!
The deactivation of the
ENABLE-SW
signal, the activation of the
DISABLE
signal, the
deactivation of
MDI2
inputs from serial link or fieldbus DO NOT GUARANTEE that the
Safe Torque Off – STO function is removed from the motor connected to the drive.
Safety stop conditions are guaranteed only when at least one of the two
ENABLE-A
and
ENABLE-B
inputs are opened.
For more details, consult the Safe Torque Off Function - Application Manual.
C153 DISABLE Input
C153
Range
0
÷
16
0
÷
24 if ES847 or ES870 is fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1153
Function
The
DISABLE
function disables the drive and overrides any
ENABLE-A and
ENABLE-B
signals
.
The
DISABLE
command sets the drive output voltage to zero, so the motor starts
idling (the motor idles and stops due to friction or the mechanical load).
If the
DISABLE
function is set up (
C153
≠
0), do the following to enable the drive:
•
deactivate the input signal on the terminal selected via
C153
•
activate the
ENABLE-A
and
ENABLE-B
signals
•
activate the
MDI2
inputs via serial link and fieldbus, if selected via
C140
,
C141
,
C142
•
activate the
ENABLE-SW
signal if programmed via
C152
.
DANGER!!!
The deactivation of the
ENABLE-SW
signal, the activation of the
DISABLE
signal, the
deactivation of
MDI2
inputs from serial link or fieldbus DO NOT GUARANTEE that the Safe
Torque Off – STO function is removed from the motor connected to the drive.
Safety stop conditions are guaranteed only when at least one of the two
ENABLE-A
and
ENABLE-B
inputs are opened.
For more details, consult the Safe Torque Off Function - Application Manual.
C154 Disable RESET Alarms on MDI3
C154
Range
0 ÷ 1
0: NO ; 1: Yes
Default
0
0: NO
Level
ADVANCED
Address
1154 bit 0
Function
If
C154
=1 : Yes
, the alarm reset function can be disabled from MDI3, that can be
assigned to other functions.
C154a ENABLE via Terminal Board Only
C154a
Range
0
÷
1
0: NO; 1: Yes
Default
0
0: NO
Level
ADVANCED
Address
1154 bit 1
Function
When
C154a=1: Yes
it is possible to force the system to consider the only
terminal physical input as the ENABLE input, independently of the active control
sources set in
C140
,
C141
,
C142
.