SINUS PENTA
PROGRAMMING GUIDE
244
/
486
P371 MPL3: Testing Variable A
P371
Range
0
÷
7
0: >
1:
≥
2: <
3: ≤
4: ABS(x) >
5: ABS(x) ≥
6: ABS(x) <
7: ABS(x) ≤
Default
0
0: >
Level
ADVANCED
Address
971
Function
This parameter defines the test to be performed for the variable detected by
P369
using
P373
as a comparing value
.
P372 MPL3: Testing Variable B
P372
Range
0
÷
7
0: >
1: ≥
2: <
3: ≤
4: ABS(x) >
5: ABS(x)
≥
6: ABS(x) <
7: ABS(x) ≤
Default
0
0: >
Level
ADVANCED
Address
972
Function
This parameter defines the test to be performed for the variable detected by
P370
using
P374
as a comparing value.
P373 MPL3: Comparing Value for Test A
P293
Range
–32000
÷
32000
–320.00 %
÷
320.00 %
% of the full-scale value of selected variable A,
Default
0
0
Level
ADVANCED
Address
973
Function
This parameter defines the comparing value with the variable selected for test A.
P374 MPL3: Comparing Value for Test B
P374
Range
–32000
÷
32000
–320.00 %
÷
320.00 %
% of the full-scale value of selected variable B
, see Table
Default
0
0
Level
ADVANCED
Address
974
Function
This parameter defines the comparing value with the variable selected for test B.