Parameter lists
AO FB:
STATUS_OPTS (15)
Storage class S; read/write capability r/w; supported modes O
Status options to determine status handling and processing
•
[UNINITIALIZED]
•
PROPAGATE FAULT BACKWARD · Status of the Transducer Block is passed on to the
upstream block over the status of BKCAL_OUT.
AO FB:
STRATEGY (3)
Storage class S; read/write capability r/w; supported modes ALL
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each
block.
Note:
These data are neither checked nor processed by the AO Function Block.
AO FB:
TAG_DESC (2)
Storage class S; read/write capability r/w; supported modes ALL
User-specific text for unique identification and assignment of the block
• Max. 32 characters, [no text]
AO FB:
UPDATE_EVT (29)
Storage class D; read capability r
Indicates whether static block data have been changed, including date and time stamp
AO FB:
XD_SCALE (12)
Storage class S; read/write capability r/w; supported modes O
Range of the OUT value (start, end, unit and decimal point)
•
0.0 to 100.0 %; specified in [%], [mm] or [degrees]
Note:
When [%] is used, the OUT value is based on the scale of 100 %. In case of [mm]
(with globe valves) or [degrees] (with rotary valves), the OUT value corresponds to the
value set in the RATED_TRAVEL parameter in the Transducer Block which is scaled as
100 %.